  1. DieselAddict

    MEP 802A Aux fuel. Thoughts on bypassing system and installing a tiger loop?

    There is no fuel cutoff solenoid for the AUX fill on the 8xx machines. If you gravity feed your AUX source it will overflow the tank in the generator.
  2. DieselAddict

    MEP 831 FAQ for owners or potential buyers

    Great Ted, Let us know how it turns out.
  3. DieselAddict

    New to me PU798A (Mep-803a on a LTT-TQG high mobility)

    The way to test for wet stacking is to add load a little at a time. Starting an AC unit is way too much load at once. You need to find that point where it struggles and hold it there till it clears then bump it up a little. 500w increments using space heaters is a good way to go. A load bank...
  4. DieselAddict

    MEP 831 FAQ for owners or potential buyers

    Can you pick up a for parts Yanmar L70 off ebay and get it going?
  5. DieselAddict

    MEP-803A in storage 14+ years

    They flushed the cooling system with oil? Does it say what kind of oil?
  6. DieselAddict

    10 kw libby mep003a making power. not running the whole house.

    Yes, you are right. L1 and L3 are the correct ones.
  7. DieselAddict

    10 kw libby mep003a making power. not running the whole house.

    Check the voltage between L2 and L3 with the generator running. You should get 240v.
  8. DieselAddict

    10 kw libby mep003a making power. not running the whole house.

    Can you explain more about how you have them hooked up? Maybe a few photos of the connections? You need to set it to 240v.
  9. DieselAddict

    10 kw libby mep003a making power. not running the whole house.

    That sounds like you have the generator set for 120v only output. What is the output switch behind the instrument panel set to (120v or 208v or 240v?) Only change the switch position with the generator off.
  10. DieselAddict

    MEP 805B on a M200A1

    And if you want to redneck it up a bit you can use your bathroom scale to weigh the tongue. Build a balance beam to split the weight keep the amount of force on the scale reasonable. https://www.etrailer.com/faq-how-to-determine-trailer-tongue-weight.aspx
  11. DieselAddict

    MEP 805B on a M200A1

    You should set the generator so you get about 10% of the total weight on the tongue. That will make sure it is stable when towing.
  12. DieselAddict

    MEP-804A single phase 120/240 conversion issue

    Yep. That would do it.
  13. DieselAddict

    MEP-804A single phase 120/240 conversion issue

    The why is because three of the windings are premenantly joined in a {edit} Y configuration inside the head. That locks you into delta only operation. What I've wanted to see is how possible it would be to trace wire 10 back into the generator head and find the connection point where the three...
  14. DieselAddict

    MEP-804A single phase 120/240 conversion issue

    The 804 has a 10 wire head. It is not possible to connect it zig-zag for single phase. You will burn it out trying.
  15. DieselAddict

    MEP 831 FAQ for owners or potential buyers

    See if this would work for you. http://www.steelsoldiers.com/showthread.php?134803-MEP-831a-Troubleshooting&p=1667559&viewfull=1#post1667559
  16. DieselAddict

    Acquired a Military surplus load bank

    I hope to be able to pick one up on the east coast when I'm done with the west coast project. It would be much more convenient than the water heater element setup.
  17. DieselAddict

    831A or 952B Questions

    You can find a few MEP-831 machines on flea-bay.
  18. DieselAddict

    Opinions on MEP-831A

    Thats a good question. I've been using the Rotella 5w40 in my air cooled engines including the 831 and they pull full load with no problem. Diesel over JP8 should not be the source of the problem. Let us know what you find out.
  19. DieselAddict

    Opinions on MEP-831A

    After you are sure you've purged the fuel system I would recommend looking at the air intake path. Black smoke is a sign of too much fuel in relation to the amount of air. An air restriction will put you down on power and make it blow black smoke. Lots of black smoke. Take a look at the intake...
  20. DieselAddict

    MEP 802 not cranking

    Excellent! Glad it was simple. The contacts on the E-stop could be a little dirty. They are self cleaning. Just cycle the button a few times.