You will probably find something major wrong with it, either bad gen head or bad motor.
Also, be more careful posting screen shots. I can see an email address and bookmarks for two credit card companies. I don't think anyone on SS would use that against you but stuff posted on the www is...
Some SX460 to 002/003 info here:
http://www.steelsoldiers.com/auxiliary-equipment/95041-c-voltage-regulator-board-repair.html
I haven't done it yet but it seems to look OK on paper. Ike is right about the 002s and 003s having a more complicated VR arrangement but it looks do-able.
Looks like G2 (battery charge 24V alternator) may feed the motor controls.
Maybe the Bridge is just there to feed the Curr Volt Xfmr for the meters? That seems to make sense.
If so, then the Bridge gets to stay and connections are...
The 002s and 003s have motor control relays (DC control circuit) and things that are powered by what? If the answer is that bridge then we'll have to look closely at what to keep and what to remove.
The Field, being a DC thing, should not matter for grounding purposes, right? It may be tied...
I'm not an expert but below are some of my opinions. Use them at your own risk. When/if I get around to fixing my 003 and if the VR is not working I plan to use an SX460. When/if that happens I plan to document it and share the knowledge. If you do not understand what is going on and the...
It has been noted that the Hardy Diesel meters are not easy to read in direct sunlight. But, for $20 they are in some ways better than the KillAWatt.
Isaac installed a SX460 on his 016. I've run a 016 with one but haven't made the install permanent, yet. Wiring on an 002 or 003 should be...
I'd try an SX460 for $60 before I spent too much on having one repaired. I'm confident I could repair them myself. If you want original then by all means fix em. If you want functional and reliable then consider a modern VR or have them totally rebuilt with new components, at least new...
I think so. A balanced load is always better but a little unbalance shouldn't hurt.
For example, if you want to run two 9A 120V loads you can plug them both into the same outlet (using the panel in this thread as example) and it would work fine. But, the generator would be happier if you...
Over 20A on either breaker will trip it before too long but you can run a 240V load and a 120V load at the same time. For example if you had a well pump that draws 5 amps 240V and a 120V device that draws 5 amps you could run both.