  1. D

    Restoration continues: Wiring Harnesses, etc. for MEP-017A

    I just picked up a 017A donor. It has been sitting a while but is mostly complete. I just want to 5kW head and maybe the bell housing so the rest is up for grabs. I also have the harness from a 016E that I gutted in good shape. Let me know exactly what you need and I'll see what...
  2. D

    MEP Generator values?

    A new 3kW commercial Yanmar powered gen is about $2500. A new 12kW commercial Diesel gen (comparable to an 003A) is $10,000+.
  3. D

    need help with starter for my 89 3 kw 24v generator

    Then you may have broken it. If nothing else there is a fan on that motor that will not cool properly if turning the wrong way. There really is no option for rotation here. The gen head doesn't care if it goes CW or CCW but the Diesel motor certainly does. I am pretty sure the oil pump will...
  4. D

    overspeeding mep 003 won't shut off

    To kill a Diesel you must shut off fuel or air or both. It is a good idea to not start a Diesel until you familiarize yourself with some sort of manual shutdown alternative.
  5. D

    need help with starter for my 89 3 kw 24v generator

    SOME Diesels will run "backward". That one will not. Get the starter straight. If you were closer I'd buy it from you. You're killing me, Smalls.
  6. D

    MEP Generator values?

    I've seen your ads on CL and your prices seem low to me. I'm not saying you should raise them. If you are happy selling for those prices then keep it up but it seem like you put a lot of effort into them.
  7. D

    MEP-016D Yanmar Model L70AE-DEGFR Technical Manual

    I do not know if those instructions exist online.
  8. D

    need help with starter for my 89 3 kw 24v generator

    The transfer pump is on the side. It has the handle for priming. It send fuel to the IP which in turn sends fuel to the injector. The injector should be on top of the motor.
  9. D

    need help with starter for my 89 3 kw 24v generator

    OK. Must be the 003 that has the electric pump that feeds the filters.
  10. D

    need help with starter for my 89 3 kw 24v generator

    Most Diesels I've worked on have 17mm injector fitting nuts. Crack it about 3/4 turn. Turn the motor over. After a short period you should get a spurt, spurt, spurt. Note: Diesel injector pumps are HIGH pressure things. You don't want the line open and spraying into space. Just loosen the...
  11. D

    need help with starter for my 89 3 kw 24v generator

    Did you crack the fuel line at the injector pump and turn it over until you get a rhythmic spurt? Can you verify that the shutdown solenoid is not engaging when it shouldn't?
  12. D

    need help with starter for my 89 3 kw 24v generator

    http://www.batterychargers.com/ProductDetail.aspx?ProductName=94026343AL $65 delivered on Amazon.
  13. D

    Pow'r Gard - Refinished

    Looks like part number for a starter is 255-70502-00. A quick search and they seem to be $500+ new.
  14. D

    Commercial Transfer Switch questions

    See pic. Are those tabs clipped or shorter or different from the other tabs that the other breakers are connected to? If so then you can't put a feed breaker there without some modification.
  15. D

    Commercial Transfer Switch questions

    The interlock could be a simple slotted metal tab and a couple of screws. Are you sure about that? It looks like there are two tabs sticking up. It should work if the empty space looks just like the spaces under the existing breakers. It is hard to tell from the pic if the connection...
  16. D

    need help with starter for my 89 3 kw 24v generator

    No problem. I am just a cog in the machine that is SS. I am glad to be able to help others and thankful for the help I get from others.
  17. D

    need help with starter for my 89 3 kw 24v generator

    Also forgot to mention there is a low fuel shutdown so if your tank is low it will not run or start. You can reach into the tank and raise the float to bypass the low fuel shutdown.
  18. D

    need help with starter for my 89 3 kw 24v generator

    Bleed the air out of the fuel filter. Prime with the electric fuel pump, if any. Then work the priming lever on the lift fuel pump. Then crack the fuel line at the injector (open about 3/4 turn) and turn the motor over until you get rhythmic spurts. Tighten the injector line and it should go...